NLA Series

Compressor-duty phase converters. Built to handle the high locked-rotor amps that scroll and reciprocating compressors draw at startup.

Overview

Compressors, air handlers, chillers, and HVAC equipment draw 6–8× their nameplate amps at startup. Standard NL converters are sized for running load — they will struggle or fail to start high-LRA compressor motors reliably. The NLA Series is engineered specifically for compressor starting duty.

NLA units are oversized relative to their rated HP to provide the starting torque and current capacity these loads require. AutoLink is standard, which is critical for compressors: if power drops and restores while the compressor is under pressure, AutoLink ensures a safe, controlled restart.

Sizing Rule for Compressors

Size to 3× the compressor nameplate HP. A 5 HP compressor needs a GP15NLA minimum.

Compressor HPConverter Model
1 HPGP3NLA
2 HPGP5NLA
3 HPGP7NLA
5 HPGP15NLA
7.5 HPGP20NLA
10 HPGP25NLA
15 HPGP40NLA
20 HPGP50NLA

Specifications

InputSingle-phase 230V, 60Hz
OutputThree-phase 230V
HP RangeGP3NLA — GP75NLA
AutoLinkStandard
EnclosureNEMA 4
WarrantyLifetime

⚠️ Do Not Use NL for Compressors

Standard NL converters are not rated for compressor LRA. Using one will result in failed starts, tripped breakers, and premature converter wear.