Problem: Converter Won't Start
Symptom
You press the start button (or apply power), but the converter doesn't spin up. You might hear nothing at all, or a brief hum followed by silence.
Possible Causes (check in order)
- No input power — Check the breaker feeding the converter. Is it tripped? Reset it. If it trips again immediately, there's a wiring fault.
- Input voltage too low — Measure L1-L2 at the converter input terminals. Should be 220–240V. If less than 210V, check your supply wiring for voltage drop (undersized wire, loose connection).
- Start capacitor failed — The converter uses run capacitors (always energized) and possibly start capacitors (energized briefly during startup). A shorted start capacitor can trip the breaker. A failed open start capacitor means no starting torque.
- Idler motor seized — If the motor is locked up (can't rotate freely by hand with power off), the bearings may have failed. Rare, but it happens on old or heavily used units.
- Overload relay tripped — Some converters include a thermal overload relay. If the unit got hot and tripped, wait 15–20 minutes and try again.
Problem: Breaker Trips When Converter or Load Starts
Symptom
The breaker trips when you start the converter, or when you start your equipment after the converter is running.
Possible Causes
- Converter undersized for the load — Most common cause. The converter draws massive inrush current when your equipment starts, and that plus the converter's own startup current exceeds the breaker trip current. Solution: up-size the converter or switch to a soft-start model like the GPX Digital Series.
- Breaker is too small — Check the breaker size against the wire and breaker table. Use a breaker sized at 250% of converter rated current.
- Starting a very hard load (compressor, HVAC) — Hard-starting loads have enormous inrush. If using the NL Series for a compressor, upgrade to the NLA Series which is optimized for this.
- Short circuit — A wiring fault in the converter or equipment wiring. Breaker trips are immediate (before the unit finishes starting).
Problem: Equipment Motor Runs Hot or Burns Out
Symptom
Your three-phase motor is running hotter than normal, trips its thermal overload, or burns out prematurely.
Possible Causes
- Voltage imbalance too high — Motor overheating is the classic symptom of voltage imbalance on the phase converter output. Measure T1-T2, T2-T3, T1-T3 with a voltmeter and calculate imbalance. If over 5%, the motor is at risk. Over 10% and you'll burn motors quickly. Fix: upgrade to PL Series or re-balance the converter.
- Converter undersized — If the converter is too small for the load, the generated leg voltage sags under load, causing the motor to draw more current to compensate — generating heat.
- Motor wired for wrong voltage — Dual-voltage motors (230/460V) must be wired for the voltage they're receiving. If a 460V-wired motor is on a 230V converter, it runs at half design voltage. This is a common mistake.
- Overloaded motor — The machine may be drawing more power than the motor is rated for. Check that cutting tools are sharp, feeds are not excessive, and the machine isn't jammed.
Problem: Voltage Imbalance Too High
Symptom
You've measured the three output voltages and the imbalance calculation is above 5% (for general loads) or above 2% (for CNC).
What's Normal
- NL Series: typically 3–7% imbalance, varies with load
- PL Series: typically <2% imbalance under load
- At no load (idler spinning, no equipment): imbalance can be higher — this is normal
Fixes
- Upgrade to PL Series — The most direct fix. Enhanced filtering maintains tighter balance.
- Ensure converter is under load when measuring — Measure balance with actual equipment running, not at no-load.
- Check capacitor values — Degraded capacitors cause worsening imbalance over time. Capacitors can be tested or replaced.
- Verify converter sizing — If significantly undersized, voltage imbalance will be worse under load.
Problem: Humming or Unusual Noise
Symptom
The converter makes noise beyond its normal running hum — clicking, buzzing, vibration, or high-pitched tones.
Possible Causes
- Normal hum (low, steady) — All rotary converters hum at 60 Hz. This is normal. If you want quieter, see the GPX Digital Series.
- Capacitor buzz — A loose capacitor or capacitor mounting bracket vibrates at 120 Hz. Tighten mounting hardware inside the enclosure.
- Contact chatter — If you hear rapid clicking, a contactor may be chattering due to low voltage or a failing coil. Check input voltage and contact condition.
- Bearing noise (grinding or squealing) — Worn bearings in the idler motor. The motor will need bearing replacement. This is a repair job — call us for service options.
- Loose panel hardware — Screws or wire ties vibrating against the enclosure. Open the panel and inspect.
Problem: Equipment Starts Slowly or With Difficulty
Symptom
Your equipment starts but takes longer than normal, or makes labored sounds during startup.
Possible Causes
- Low voltage on generated leg (T3) — The generated leg voltage may be significantly lower than T1/T2, reducing starting torque. Measure voltages.
- Converter undersized — Not enough capacity to provide full starting current. The equipment starts but weakly.
- Cold weather — In cold temperatures, motor insulation resistance drops and bearing grease stiffens. This is most noticeable in compressors. Let the converter warm up for a few minutes first.
- Degraded run capacitors — Capacitors lose capacitance with age. Old capacitors may not provide enough reactive power for reliable starting.
Quick Diagnostic Reference
| Symptom | Most Likely Cause | First Action |
|---|---|---|
| Won't start, no hum | No input power | Check breaker and L1-L2 voltage |
| Hums but won't spin up | Start capacitor failed or undersized | Check/replace start capacitors |
| Breaker trips at start | Undersized for load or breaker too small | Check converter sizing and breaker rating |
| Motor overheating | Voltage imbalance or undersized converter | Measure T1-T2-T3 voltages under load |
| High voltage imbalance | Degraded caps or wrong converter for CNC | Check capacitors; consider PL Series |
| Grinding noise | Bearing failure in idler motor | Schedule bearing replacement |
| Slow starting | Low T3 voltage or undersized converter | Measure T3 voltage; check converter sizing |
Can't find the problem?
Call us at (800) 417-6568. We diagnose converter problems over the phone regularly — have your converter HP, voltage measurements (if you have a meter), and equipment description ready.